ÖÇÄܵç»úÆô¶¯Æ÷´ø×Ô¶¯ÏàÐòУÕý

¿í¶È£º22.5 mm
ÏàÊý£ºÈýÏà
¸¨Öúµçѹ£ºDC 24 V
¸ºÔصçѹ¿É´ï£º3AC 200-480 V
¸ºÔصçÁ÷¿É´ï£º9 A

  • UG 9256/807
¿í¶È£º22.5 mm ÏàÊý£ºÈýÏà ¸¨Öúµçѹ£ºDC 24 V ¸ºÔصçѹ¿É´ï£º3AC 200-480 V ¸ºÔصçÁ÷¿É´ï£º9 A... more

²ÎÊý

Width: 22,5 mm
1- / 3-phase: 3
Auxiliary voltage: DC 24 V
Load voltage up to: 3AC 200 - 480 V
Load current up to: 9 A
On/Off Input Control: DC
Signalling output: Yes
Temperature monitoring: Yes
Type: UG 9256/807

ÓÅÊÆ

  • Up to 4 functions in one unit
    - Providing clockwise phase sequence at the motor connection terminals
    - Phase failure detection
    - Motorprotection Class 10 A, Class 5
    - Softstart
  • Galvanic mains separation by forcibly guided contacts contact opening min. 0.5 mm (UG 9256/807)
  • 66 % less space
  • Simple and time-saving commissioning as well as user-friendly operation through setting via potentiometer on absolute scale
  • Hybrid relay combines benefits of relay technology with non-wearing semiconductor technology
  • High availablility by
    - Temperature monitoring of semiconductors
    - High withstand voltage up to 1500 V
    - Load free relay reversing function

ÌØÕ÷

  • According to UL 60947-4-2, IEC/EN 60947-4-2
  • To reverse the rotary field
  • For 3-phase motors with rated motor current from Ie 0.1 A ... 0.5 A or 0.5 ... 2 A or 1.5 A ... 9 A
  • 1 potentiometer f¨¹r setting of rated motor current
  • 3 LEDs for status indication
  • Reversing with relays without current, switching with thyristor
  • Galvanic separated 24V-inputs for clockwise
  • Reset button on front
  • Connection facility for external reset button
  • Relay indicator output for operation
  • Galvanic separation between control circuit and power circuit
  • Galvanic separation of motor terminals from mains voltage in off state or fault condition (UG 9256/807)
  • Width 22.5 mm