°²È«¼ÌµçÆ÷

  • OA 5603/39__L1
... more

²ÎÊý

Contact equipping: 8
Continuous current: 6 x 10 A
Nominal voltage: DC 6 - 110 V
Voltage Range UN: 0,75 - 1,4
Protection type: RT II (flux-proof relay), optional RT III (wash-tight)
Size L x W x H: 77,1 x 20 x 39,5 mm
Test voltage (AC) contact set - coil: ¡Ý 4 kV eff
Type of relay: Monostable
Temperature range (- / +): -40 - 75 ¡ãC
Type acc. to DIN EN 61810-3: A
Approvals: TÜV
Contact material: AgSnO2, AgNi
Clearance and creepage distances, contact set - coil ¡Ý: 8 mm
Relay type: OA 5603/39__L1

ÓÅÊÆ

ÌØÕ÷

  • Acc. to DIN EN 61810-1, DIN EN 61810-3 (Type A), DIN EN 50578 (UIC 736)
  • With forcibly guided contacts
  • High switching reliability due to crown contacts
  • Clearance and creepage distances:
    contact - coil ¡Ý 8 mm
    contact - contact ¡Ý 5.5 mm
    Double and reinforced insulation with pollution degree 2
    Overvoltage category: III
  • High voltage resistance ¡Ý 4 kV
  • High mechanical service life
  • High temperature range: - 40 ... + 75¡ãC
  • High continiuous thermal current Ith = 10 A